Marine Portable Fire Extinguisher Supply, Annual Servicing & Hydrostatic Testing India
Seanav Marine performs statutory marine fire extinguisher supply, annual inspection, refilling/recharging, and hydrostatic pressure testing for marine portable and wheeled fire extinguishers across all Indian commercial ports. We supply and service Dry Chemical Powder (ABC/BC), CO2, Mechanical Foam, Water, Water Mist, and Wet Chemical fire extinguishers compliant with IMO Resolution A.951(23) and NFPA 10.
Supported OEM Equipment & Multi-Make Coverage
Send the equipment make and model so we can confirm the scope and parts availability.
Technical Specifications & Operational Coverage
| Extinguishers Supplied & Serviced | Dry Chemical Powder (DCP 1kg to 12kg portable, 25kg/50kg wheeled), CO2 (2kg, 5kg portable, 45kg wheeled), Mechanical Foam (9L portable, 45L/135L wheeled), Water & Water Mist (9L), Wet Chemical Deep Fryer (6L/9L) |
|---|---|
| Standard | SOLAS Chapter II-2 Reg 10, IMO Resolution A.951(23), NFPA 10 |
| Hydrostatic Test Interval | 5 years for CO2 cylinders; 5 to 10 years for pressure-retained dry powder and foam bodies |
| Supply & Consumables | New certified marine extinguishers, foam refills, dry powder chemical charges, internal propellant gas cartridges, spare horns and discharge hoses |
Standard 5-Step Portable Extinguisher Statutory Service SOP
Our Class-approved technicians execute this standardized procedural workflow to ensure first-time compliance with attending Class surveyors and Indian Port State Control (PSC) inspectors:
-
Physical Inspection & Pressure Gauge Calibration
Inspect cylinder bodies for exterior corrosion, dents, or damaged horns; verify pressure gauge reading is inside green operable zone.
-
Gross Weight Check & Internal Gas Cartridge Inspection
Weigh CO2 extinguishers on calibrated scales to verify <10% weight loss; inspect internal propellant gas cartridges.
-
Discharge Hose & Nozzle Obstruction Clearance
Blow dry air through discharge hoses, nozzles, and shut-off handles to eliminate obstructions and verify gasket elasticity.
-
Periodic Hydrostatic Pressure Proof Testing
Subject cylinders due for hydraulic test to 1.5x test pressure in approved hydrostatic test chamber with expansion measurement.
-
Service Tagging, Tamper Pin Sealing & Certificate Delivery
Affix durable weather-resistant inspection label, seal safety pin with tamper-evident plastic seal, and issue Class certificate.
24/7 Port & Anchorage Attendance Across India
Seanav Marine provides rapid shore-based and offshore launch boat boarding across all 170+ Major and Minor Indian Ports, including:
Certified Equipment & Replacement Spares in Stock
Seanav Marine maintains bonded warehouse spare parts inventory across major Indian ports for immediate dispatch and installation during port calls:
Download Marine Portable Fire Extinguisher Log & Checklist
Standardized format for Second Officers to record monthly extinguisher inspections and hydrostatic dates.